We see many inquiries on MV URD cables where a customer wants MV-105 rated URD. 

We see many inquiries on MV URD cables where a customer wants MV-105 rated URD. These inquiries are usually in response to a competitor's spec where the EPR URD indicates:

    - 105C continuous operating temperatures
    - Can be listed by UL as Type MV-90 on special orders
    - Improved temperature rating (Insulation system has been tested and qualified for operation at 105C continuous and 140C emergency operating temperature)

Our MV URD for EPR/CN/LLDPE indicates designed to operate continuously at a conductor temperature not exceeding:

    - 105C for normal operations
    - 140C for emergency overload
    - 250C for short circuit

Our default is to mark the jacket with Type MV-90 (UL) and competitor specs may list this marking as optional. Of note, the 105C insulation performance is defined by ICEA and UL as listed above for LLDPE jacket.

Overall, these products are rated with a continuous operating temperature not to exceed 105C and none of our competitor's spec (nor ours) indicate that the product will be market 'UL MV-105'. The only UL marking that any manufacturer can put on the print legends of these products is MV-90.

When comparing to competitor specs the way they are written can be confusing, but essentially they provide the same product as LS.
By LS Engineering October 24, 2024
Q: What is the difference between 1350 Aluminum and 8000 Series Aluminum Alloy?
By LS Engineering October 24, 2024
Q: What kind of material is used for strand filler in your filled strand primary cable? Is it a powder, gel or something different? Is the same strand material for all sizes and both copper and aluminum?
By LS Engineering March 28, 2024
Q: Where do I find standard reel sizes and protective coverings? How do I specify a specific reel size? What is the difference between CL1, CL2 and CL3 wooden reels?
By LS Engineering March 28, 2024
Q: Can LS manufacture MV URD EPR with an XLPE jacket?
By LS Engineering September 22, 2023
Q: Is LS MV-105 cable UL Listed or only UL Compliant?
By LS Engineering September 21, 2023
Q: Does LS offer low smoke, zero halogen (LSZH) cables?
By LS Engineering September 21, 2023
Q: Do we have a cross reference for LS LV tray cables and Belden?
By LS Engineering September 15, 2023
Q: Is your MV-105 with PVC jacket flame retardant?
By LS Engineering September 14, 2023
Q: Can we offer a 15kV 750MCM AIA three conductor with a 4/0 ground?
By LS Engineering September 14, 2023
Q: How can I tell if a part number / product description listed in the Inventory look up on the sales portal is for a standard product?
Show More
Share by: