Ask an Engineer

Have a Technical Question?

A cornerstone of our world-class customer service is to ensure you have the answers you need to keep your project running smoothly. It's our job to provide 24/7 technical support, and our team is ready to help. Our team has the best turnaround time for technical support in the industry and it reflects with the satisfaction of our customers.

Don't hesitate to reach out to LS directly. We take pride in providing personalized support from our expert engineering team. The engineering team will work closely with you to understand your specific needs and provide tailored solutions and guidance. Email us today!

Didier "Kaz" Kaczmerek
Applications Engineer II
252-824-3541 | Email

 

Technical Support

LS Cable & System USA makes customer inquiries public for the common good. If you have any questions about our products, services, or specs, you may find the answer below. Our knowledgeable engineers have compiled a handy Q&A to make it easier for customers to find the information they need.

A: It’s not designed to be a current-carrying conductor. The main purpose is to reduce the electrical stress on insulation. But in fault conditions, it can act as a short circuit current carrying path and maximum capability depends on the calculation per ICEA P-45-482. (But it all depends on several factors being met at certain categories and criteria)




 

A: VLF testing according to the NETA and IEEE 400.2 is done after cable installation typically by a third party testing company at the cable installation site. This testing may be contracted between the general contractor and project owner.

LS Cable & System USA MV test procedures:

In general, there are three types of electrical tests that are performed during the service life of a medium voltage cable.

Installation Testing
This is a field test that is completed after installation but before splicing & termination. This test is performed to detect any possible damage caused while installing the cables.


Acceptance Testing
This test is completed after cables have been installed and all splices and termination have been completed, but before cables have been energized. This test primarily exposes faulty splices and terminations.


Maintenance Testing
This field test is made during the operating life of the cable. The test is conducted to determine the deterioration of the system and to check the serviceability life of the cables. After evaluating the information,
appropriate maintenance can be scheduled as necessary.


LS Cable & System USA cables are manufactured to high standards and tested rigorously in order to relieve end users of the burden of pre-installation testing. In normal situations, such testing is not necessary and the cable can be installed, as received, with confidence. However, pre-installation testing should be conducted if the customer specification requires it or if there is evidence of cable mishandling or damage.

Per IEEE Std 400 IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above, the recommended field test procedures for medium voltage cables (extruded dielectric) are:

IEEE 400.2 - IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF)(less than 1 Hz)

IEEE 400.3 - IEEE Guide for Partial Discharge Testing of Shielded Power Cable Systems in a Field Environment

IEEE 400.4 - IEEE Guide for Field Testing of Shielded Power Cable Systems Rated 5 kV and Above with Damped Alternating Current (DAC) Voltage

Any of the three methods above are acceptable for installation, acceptance and maintenance testing. DC Withstand (Hi-Pot) Testing is not recommended for extruded dielectric cables, particularly for field-aged cables. Past studies have shown that the electrical life of the cable can be greatly reduced due to the additional electrical stresses caused by using a DC Hi-Pot Test. Further information on this subject is available in EPRI Report TR-101245 “Effect of DC Testing on Extruded Cross-Linked Polyethylene Insulated Cables”

Procedures from the MV Installation guide.pdf

 

A: As a metal material, aluminum plays an essential role in different industries. It's flexibility, durability and light weightiness have made it a go-to option for many engineers, designers and manufacturers. However, not all aluminum types are the same. In particular, 1350 and 8000 aluminum alloys have distinctive properties that make them suitable for various functions.

 
What is 1350 Aluminum?
This alloy has a purity of 99.5% and is often used in electrical applications. One significant advantage of 1350 aluminum is its high electrical conductivity rating, making it an excellent choice for electrical wiring, transformers, and other electrical components. Additionally, its malleability makes it easily formed and shaped, making it an ideal material for intricate components.
 
What is 8000 Series Alloy Aluminum?
8000 aluminum alloy is made by mixing aluminum with copper, manganese, and other metals. Unlike 1350 aluminum, it is not primarily used for electrical applications. Instead, it's commonly used in aerospace and manufacturing due to its strength and durability. Parts made with 8000 aluminum often withstand high-stress environments and are used in constructing aircraft, trucks, and other vehicles.
 
Another significant difference between these two aluminum alloys is their corrosion resistance. 1350 aluminum is quite susceptible to corrosion, so corrosion resistance is crucial in applications that are not recommended. In contrast, 8000 series aluminum alloy is highly corrosion-resistant and can withstand harsh environments. One particular area where the two aluminum alloys are similar, however, is in terms of their weldability. Both 1350 and 8000 series aluminum are relatively easy to weld, making them a preferred choice.
 
Per the National Electrical Code (NEC), low voltage (2kV or less) aluminum conductors must be made of 8000 series aluminum alloy. The reasoning behind this is that 8000 series aluminum has better creep resistance compared to 1350. This makes them better for terminations, where the heating and cooling of the conductors can cause terminations to loosen over time. 8000 series aluminum behaves more like copper in this regard and results in more stable terminations. For medium voltage cable, both 1350 and 8000 series can be used. The logic here is that medium voltage terminations are more robust than low voltage, and the termination technicians are more highly skilled, mitigating the risk posed by 1350. However, 8000 series still results in a more stable connection which is why some customers require it even for MV cable. Although 8000 series aluminum is still required by the NEC for low voltage, 1350 remains the preferred choice for medium voltage due to its lower cost and better process capability.

There were issues with 1350 aluminum conductor terminations when aluminum conductors were first deployed as building wire (low voltage, 600V) in the 1960's. This problem was solved by transitioning the aluminum used in building wire from 1350 to 8000 series alloy which has lower creep values than 1350, an improving the termination design. This was not an issue for medium voltage (MV).
 
All U.S. national standards, as well as the NEC, allow 1350 for MV cables.
eqa16

 

A: NEMAWC26 / EEMAC201 the BINATIONAL WIRE AND CABLE PACKAGING STANDARD contains reels and packaging for use in the United States and Canada.
 
Q: How do I specify a specific reel size?
 
A: Reels are designated by the dimensions (in inches) of the Flange x Inside Traverse x Drum (i.e.: 96x4x56).
 
eqa14

 

A: LS MV-105 products are UL Listed. UL Certificate of Compliance attached below.

eqa12

 

A: LS does not have a low smoke, zero halogen (LSZH) compound for any of our cables. Also of note, UL nor ICEA offer this compound for MV cable.

A: Yes, we can manufacture LV tray cables similar to Belden, but with notable exceptions (see below):

Type|LS Cable E-Series|Exceptions
TCXH12/3G | E3BFA-121B03CE00 | CSA, FT-4 RATING
TCXH6/3G|E3BFA-061B03CE00|CSA, FT-4 RATING
TCXH4/3G|E3BFA-041B03CE00|CSA, FT-4 RATING
TCXH10/4G|E3BFA-101B04CE00|CSA, FT-4 RATING
4C16 TC-ER|NO QUOTE|EPR, CPE JACKET
5C16 TC-ER|NO QUOTE|EPR, CPE JACKET
19C16 TC-ER|NO QUOTE|EPR, CPE JACKET
1118A|E1BEB-161B01PJ00|NPLF*, EU**
1055A|E1BED-161B02PJ00|NPLF*, EU**
1039A|E1BED-161B04PJ00|NPLF*, EU**
1119A|E1BEB-161B01TJ00|NPLF*, EU**
7806R|NO QUOTE|COAXIAL CABLE
 
*NPLF - Non-power limited signaling cable manufactured by Belden and distributed by Allied. NPLF fire alarm cable is rated 150V, 75 C. It is non-conduit cable for indoor use, according to NEC standards.
**EU - European Union.

A: Yes, our MV cables meet UL 1685 Flame Exposure test per UL 1685 as noted in our catalog.

eqa9

 

A: In the image below, the red boxes indicate the industry specification that products are manufactured to. If there is a spec reference other than ULXXXX or ICEAXXXX, it is a non-standard product. A non-standard product may have different colors, markings, dimensions, compound, etc. per a customer's request or specification.

eqa7

 

A: We do not offer MV-105 CTS with EPR jacket. EPR is an insulation material, not jacket material. Our Engineering team advises that a different EPR compound may be formulated for use as jacketing material (see below), but our current EPR compound is not and does not meet the standards we currently manufacture to (UL and ICEA). Of course, a customer may choose not to have it meet the standards we manufacture to, but it is unlikely that we source an additional jacket material unless there was a substantial upside.

eqa6

 

We see many inquiries on MV URD cables where a customer wants MV-105 rated URD. These inquiries are usually in response to a competitor's spec where the EPR URD indicates:

  •  105C continuous operating temperatures
  • Can be listed by UL as Type MV-90 on special orders
  • Improved temperature rating (Insulation system has been tested and qualified for operation at 105C continuous and 140C emergency operating temperature)

Our MV URD for EPR/CN/LLDPE indicates designed to operate continuously at a conductor temperature not exceeding:

  • 105C for normal operation
  • 140C for emergency overload
  • 250C for short circuit
Our default is to mark the jacket with Type MV-90 (UL) and competitor specs may list this marking as optional. Of note, the 105C insulation performance is defined by ICEA and UL as listed above for LLDPE jacket.

Overall, these products are rated with a continuous operating temperature not to exceed 105C and none of our competitor's spec (nor ours) indicate that the product will be market 'UL MV-105'. The only UL marking that any manufacturer can put on the print legends of these products is MV-90.

When comparing to competitor specs the way they are written can be confusing, but essentially, they provide the same product as LS.

A: Yes, LS packages reels with a level 2 reel wrap which provides adequate protection for storing reels in outdoor or inclement weather (see below).

Typically, additional packaging materials are required for cable that will be stored outside. See NEMA WC 26, 2008 Edition, 2008 - BINATIONAL WIRE AND CABLE PACKAGING STANDARD

This standard covers uniform requirements for packaging electrical wire and cable and replaces the following NEMA/EEMAC standards

eqa4(1)

eqa4(2)

 

A: Coated copper is generally copper plated with another metal to improve performance; i.e. nickel plated copper (high temperature), silver plated copper (better electricals), etc. Our tin-plated copper drain wires per ASTM B33 prevent the galvanic reaction between copper drain wire and aluminum laminated tape.

A: Copper Tape Shield (CTS) is considered metallic shielding for our E8 / UL1072 (MV-105) cables. TC-ER is a UL listing for Tray Cables that have passed the additional "ER testing" for impact and crush resistance, usually attached to our PLTC/ITC, low voltage instrumentation, control and power cables (E1, E2 and E3). LS does not have a specific TC-ER UL listed cable that uses CTS. Many of our larger E8 cables can be used for tray cables (CT USE). TC-ER does not apply to CTS cables but the CTS cables 1/0AWG and larger can be installed in cable trays.

For Example:

eqa2

 

A: Our VFD cables use a copper tape over XLPE conductors, so yes, we have the capability to make this cable. Tape thickness is 10mil vs. our standard 5mil. It is odd that there is no ground wire in contact with the shield, perhaps the metal tape is for rodent control? Please note that we are not currently quoting VFD cables at this time.